ATC3C2X30200
Automatic Transfer Switch
200 amp, 3-phase, 3 Poles, NEMA 1 indoor
with generator exerciser
(single phase, 2 or 4 pole, NEMA 3R optional)
Yes, we can export this product to most other countries!
Product Description
The Eaton Cutler-Hammerฎ Automatic Transfer Switch from Eatons electrical business is designed to provide unmatched performance, reliability and versatility for critical standby power applications. The switches can be equipped with the ATC-100 or ATC-300 controllers to match your application needs. All the controllers offer rock-solid monitor-ing, status reporting and transfer control operation. Superior design and robust construction make Eatons Cutler-Hammer transfer switch the industry benchmark for critical and distributed power systems. Assembled in Mexico with USA components.
Electrical Ratings
Ratings 100, 200, 225, 260, 400 and 600 amps.
2, 3 or 4-poles.
Up to 600 Vac, 50/60 Hz.
NEMA 1, 3R, 12, open.
UL 1008 listed.
CSA C22.2 No. 178 certified.Industrial Design Highlights
Double-throw, mechanically interlocked
transfer mechanism.
Seismic Zone 4 qualified
(BOCA, CBC, IBC, UBC).Standard Features
Auxiliary relay contacts:
Source 1 Present 2NO and 2NC
Source 2 Present 2NO and 2NC
Switch position indication contacts:
Source 1 Position 1NO and 1NC
Source 2 Position 1NO and 1NC
Source 1 and Source 2 sensing:
Undervoltage/underfrequency
Overvoltage/overfrequency
3-phase rotation protection
3-phase voltage unbalance/loss
Pre-transfer signal contacts 1NO/1NC.
Go to Emergency (Source 2).
Seven field-programmable time delays.
LCD-based display for programming, system
diagnostics and Help message display.
Mimic diagram with source available and
connected LED indication.
Time-stamped history log.
System test pushbutton.
Programmable plant exerciser -- OFF, daily,
7, 14, 28-day interval selectable, run time
0-600 minutes, no load/load with fail-safe.Optional Features
Available TVSS surge suppression for
power/controller, engine start circuit,
phone and cable connections.
Field-selectable multi-tap transformer
panel permits operation on a wide range
of system voltages.
Space heater with thermostat.
Ammeter -- load side.
Stainless steel cover for controller.
Specs
Switch Current Rating | 200 amps |
Voltage Ratings (field selectable) | many including 120, 208, 240, 480V 60Hz, 1 or 3 phase |
Operating Temperature (controller) | -20 to +70C (-5 to +158F) |
Operating Humidity | 95% relative humidity, non-condensing |
Control Features (see Note 1)
see spec sheets for additional details |
- start time delay: 0-120 seconds - transfer time delay: 0-1800 seconds - retransfer time delay: 0-1800 seconds - time delay generator fail: 0-8 seconds - stop time delay: 0-1800 seconds - time delay neutral: 0-120 seconds - time delay voltage unbalance: 10-30 seconds - voltage unbalance: 5% - 20% - voltage & frequency sensing of both sources 50-97% D.O. undervoltage 54.0-58.2Hz D.O. underfrequency 105-120% overvoltage 61.8-66.0Hz overfrequency |
Exerciser Clock | 1, 7, 14, 28 day interval at no load or load 0-600 minute run-time |
Position Indication | (4)LEDs and LCD Display on door |
Spare Auxiliary Contacts | (2) Form C (1 Emergency, 1 Normal) |
Battery Charger | not included (order separately if required) |
UL Withstand & Closing Ratings | 10,000 amps when used with any circuit breakers Higher when used with specific Cutler-Hammer breakers |
Lug Capacities | 250MCM to #6 AWG per pole |
Nominal Dimensions (H x W x D) | 38.7" x 18.3" x 13.4" with door closed |
NOTES:
1) The start time delay prevents nuisance generator starts during momentary utility power variations; transfer time delay allows generator set to stabilize before load is applied; retransfer delay prevents needless power interruption if return of utility power is momentary; stop delay allows gradual generator set cool down; undervoltage sensing of utility supply provides reliable starting of generator set during brownout conditions.
2) This switch is NOT service entrance rated. The NEC normally requires a separate service entrance rated disconnect between this switch and your utility meter.
3) The ATC contactor comes standard with 2 or 3 power poles to switch the hot leads of a single phase or 3 phase system. It does NOT switch the neutral, which is acceptable in most areas of the USA. See article 250.20 of the 2002 NEC. If there are special requirements in your area that require switching the neutral (as dictated by local codes or electrical inspectors) you must specify an additional power pole using the dropdown menu below when ordering.
4) This switch provides a single isolated contact for controlling the genset. The contact closes when the genset is to start and run.
Customers who purchased this product also ordered:
(click underlined words to see product pages)
Battery charger BATTEND022
Select options using drop-down menus. Price adders for extra options will be automatically included in price shown by shopping cart.
Item Number: ATC3C2-200
Price: $2,821
Price last updated 11/1/2023
Shipping Weight: 164 lbs.