Page last updated Nov 7, 2023 @ 09:56pm
HUPS-6 UPS System
DISCONTINUED
SEE ALTERNATIVE SYSTEMS AT THIS LINK
House UPS System
6000VA/4200 watt, 120/240VAC
Our House UPS systems fill a market niche between portable generators and automatic standby generators. Most power outages last less than a couple hours and these systems easily provide backup AC power for that length of time. These systems are silent and fully automatic and transfer extremely fast when line power is lost. No more guessing how long an outage will last and whether it is worth the trouble to drag out that portable generator. For most outages which are short this system eliminates that trouble!
Or use this system with an automatic standby generator to continue to provide power while the generator is starting.
For details about how this system operates and its advantages click here.
What is included in the NoOutage.com House UPS System?
We provide everything you need to install an operational system except for one circuit breaker that must be installed in your load center breaker panel and a connected wall outlet. If you want to be able to provide backup power for a long-term power outage you will also need a portable or standby generator (not included). System includes the following:
* UPS Module * Output Transformer * Transfer Switch - 10 circuit * interconnecting AC jumper cables |
* AC Input Cord - 25' with NEMA L1430P
Plug * AC Output Cord with NEMA L1430C Connector * interconnecting battery jumper cables * gel cell maintenance-free lead acid batteries (in UPS) * battery charger (in UPS) |
We do not provide the circuit breaker for your load center panel due to the many brands of panels. Purchase one locally that fits your panel. It should be rated 30 amps. Your installer will also need to wire this breaker to a 30A 120/240VAC NEMA L1430R wall receptacle near the UPS.
System Specs
System AC Line Input Voltage | 240VAC nominal, other voltages available | |
System AC Line Input Frequency | 60Hz nominal, 40-70 Hz range | |
AC Line Circuit Capacity | 30 amps 240VAC | |
Portable Generator Size (optional) NOTE 1 | 7500 Watts rated w/ 30 amp 240VAC L1430R receptacle | |
Inverter Power Output Rating | 6000VA / 4200 Watts continuous 110% for 300 seconds 130% for 30 seconds |
|
System output voltage (on inverter) | 120/240VAC +5% pure sine wave <5% THD |
|
Typical System efficiency | 92% | |
Approximate Battery
Run-Time at average 50% load See NOTE 4 |
internal battery only | 14 minutes |
1 optional external battery module | 41 minutes | |
2 optional external battery modules | 79 minutes | |
3 optional external battery modules | 125 minutes | |
4 optional external battery modules | 179 minutes | |
Environmental Ratings | 32F to 104F operating (78F optimal for battery life) | |
Warranty by Manufacturer | - 3 years electronics and batteries | |
Certifications | UL Listed, cUL, FCC |
|
NOTES: 1 - Oversized generators with automatic voltage regulators work best. 2 - 3 - Under normal conditions batteries should last at least 3-5 years. Replacement batteries are available and can be installed by user. 4 - Battery run-time is not linear. At half the stated electrical load the run-time will be MORE than double the original value. |