Panelboard
series P1
AC Panelboard Configurator
Siemens series P1
480Vac or 250Vdc 400A max
These Siemens panelboards are available with a wide range of configurations built to order with short lead times. The P1 series can be ordered for up to 480Y/277V ac 400A single and three phase. DC panels are also available at 12V, 24V, 48V, 125V and 250V for use with dc rated 2 pole breakers rated at 14kAIC(contact us for higher DC interrupting ratings). Perfect for most lighting and small power distribution applications. Click for manufacturer's catalog information.
Follow the instructions below for instant pricing and ordering.
To avoid confusion please submit separate orders for multiple panels.
STEP #1: Select the type of panel and basic options
STEP #2: Select main breaker
STEP #3: Select branch breakers
STEP #4: Select up to one subfeed breaker
STEP #5: Select other options
STEP #1: Select the type of panel and basic options and add to cart | |
Main Lug Only (MLO) | Main Breaker (MB) |
STEP
#2: MAIN BREAKER (Skip this step if panel is MLO) * Select one main breaker and add to cart. * Be sure to select a breaker frame Amp rating and trip rating that is within the panel bus Amp rating. * Also select breaker with a Voltage and interrupting rating that matches or exceeds the panel specified in Step #1. |
||||||
Panel Bus Amp Rating |
Breaker Type | 240Vac Interrupting Rating (kA) | 480/277Vac Interrupting Rating (kA) | 250Vdc 2-pole Interrupting Rating (kA) | Catalog Number | Order Button |
100 | BL std @ 240V |
10 | don't use for this voltage | don't use for this voltage | BL | |
100 | BLH | 22 | don't use for this voltage | don't use for this voltage | BH | |
100 | BQD std @ 480V |
65 | 14 | 14 | BQ | |
125 | NGB standard |
100 | 25 | 14 | NB | |
125 | ED4 | 65 | 18 | 30 | E4 | |
125 | HED4 | 100 | 42 | 30 | H4 | |
125 | HHED6 | 100 | 65 | don't use for this voltage | HA | |
Panel Bus Amp Rating |
Breaker Type | 240Vac Interrupting Rating (kA) | 480/277Vac Interrupting Rating (kA) | 250Vdc 2-pole Interrupting Rating (kA) | Catalog Number | Order Button |
225 | QJ2 std @ 240V |
10 | don't use for this voltage | don't use for this voltage | QJ | |
225 | QJH2 | 22 | don't use for this voltage | don't use for this voltage | QH | |
225 | QJ2-H | 42 | don't use for this voltage | don't use for this voltage | Q2 | |
225 | HQJ2H | 100 | don't use for this voltage | don't use for this voltage | HQ | |
225 | FXD6 | 65 | 35 | 30 | FX | |
225 | HFD6 | 100 | 65 | 30 | HF | |
225 | HHFD6 | 200 | 100 | don't use for this voltage | H1 | |
Panel Bus Amp Rating |
Breaker Type | 240Vac Interrupting Rating (kA) | 480/277Vac Interrupting Rating (kA) | 250Vdc 2-pole Interrupting Rating (kA) | Catalog Number | Order Button |
250 | FXD6 standard |
65 | 35 | 30 | FX | |
250 | HFD6 | 100 | 65 | 30 | HF | |
250 | HHFD6 | 200 | 100 | don't use for this voltage | H1 | |
400 | JXD6 standard |
665 | 35 | 30 | JX | |
400 | HJD6 | 100 | 65 | 30 | H6 |
STEP
#3: BRANCH BREAKERS
* Select all the branch breakers and quantities and add to cart. * Be sure to select branch breakers that have Voltage and interrupting ratings that match or exceed the panel specified in Step #1. * Do not select more branch breakers than will fit in the available pole spaces for the panel. * Single phase panels cannot accommodate 3 pole breakers. * Use 2 pole dc rated breakers in dc panels. |
|||||||
Breaker Type | 120Vac Interrupting Rating (kA) | 120/240Vac Interrupting Rating (kA) | 240Vac Interrupting Rating (kA) | 277Vac Interrupting Rating (kA) | 480/277Vac Interrupting Rating (kA) | 250Vdc 2-pole Interrupting Rating (kA) | Order Button |
BL | 10 | 10 | don't use for this voltage | don't use for this voltage | don't use for this voltage | don't use for this voltage | |
BLH | 22 | 22 | don't use for this voltage | don't use for this voltage | don't use for this voltage | don't use for this voltage | |
HBL | 65 | 65 | 65 | don't use for this voltage | don't use for this voltage | don't use for this voltage | |
BLF(GFCI) | 10 | don't use for this voltage | don't use for this voltage | don't use for this voltage | don't use for this voltage | don't use for this voltage | |
BLHF(GFCI) | 22 | 22 | don't use for this voltage | don't use for this voltage | don't use for this voltage | don't use for this voltage | |
BQD | 65 | 65 | 65 | 14 | 14 | 14 use 2 pole for dc |
|
NGB | 100 | 100 | 100 | 25 | 25 | 14 use 2 pole for dc |
STEP
#4: SUBFEED BREAKER (optional) |
|||||
Breaker
Frame Amp Rating |
Breaker Type | 240Vac Interrupting Rating (kA) | 480Vac Interrupting Rating (kA) | 250Vdc 2-pole Interrupting Rating (kA) | Order Button |
125 | ED4 | 65 | 18 | 30 use 2 pole for dc |
|
125 | HED4 | 100 | 42 | 30 use 2 pole for dc |
|
125 | HHED6 | 100 | 65 | don't use for this voltage | |
225 | QJ2 | 10 | don't use for this voltage | don't use for this voltage | |
225 | QJH2 | 22 | don't use for this voltage | don't use for this voltage | |
225 | QJ2H | 42 | don't use for this voltage | don't use for this voltage | |
225 | HQJ2H | 100 | don't use for this voltage | don't use for this voltage | |
Breaker
Frame Amp Rating |
Breaker Type | 240Vac Interrupting Rating (kA) | 480Vac Interrupting Rating (kA) | 250Vdc 2-pole Interrupting Rating (kA) | Order Button |
250 | FXD6 | 65 | 35 | 30 use 2 pole for dc |
|
250 | HFD6 | 100 | 65 | 30 use 2 pole for dc |
STEP #5: If required select one or more of the following and add to cart. | |
Description |
Order Button |
.