Automatic Transfer Switch
100 amp, 120/240V, 1-phase
generator exerciser

 

Description

The RSS Automatic Transfer Switch combines dependability and flexibility in a small, economical package. RSS switches are suitable for standby power systems in residential and light commercial applications. The RSS100 and RSS200 products are built to satisfy the back up power requirements of virtually any residential or light commercial application.

The RSS products are Listed to UL 1008, the Standard for Transfer Switch Safety. Cummins products adhere to National Electrical Code (NEC) and National Fire Protection Association (NFPA) requirements.

RSS transfer switches monitor utility power 24 hours a day and 7 days a week. When utility power becomes unsatisfactory or fails; the controller signals the generator to start, then transfers the load. When stable utility voltage returns, the transfer switch will automatically switch electrical load from the generator to the utility. No action is required by the user.

Features

Mechanically interlocked contactor
- A powerful and economical solenoid drives the mechanism
- Long-life, high pressure, silver alloy contact resists burning and pitting

Fully automatic control
- User-friendly front panel is configurable without special tools
- 12 hour exercise offset-Selectable exercise at repeatable intervals

Neutral and ground bar
- Fully rated
- Silver plated copper ground and neutral bus

Ease of connection
- Solderless screw type terminals for external power connections

PowerCommand® microprocessor control

PowerCommand® 20 control – A versatile, feature rich microprocessor-based control with LCD digital display and tactile-feel soft-switches for easy operation and screen navigation. Please see the PowerCommand® 20 control specification sheet S-6562 for the full description, benefits and features.


Specifications

Switch Current Rating 100 amps, 2 pole
Voltage Rating 120/240V, 1 phase, 60Hz standard (50Hz if controller setting changed in field)
Control Features (see notes below)

Detailed instructions contained in Owner Manual.

KEY:
P.U. = pickup
D.O. = dropout
Function Adjustable Range Factory Setting
start time delay1 0-10 sec adj 3 sec
transfer time delay2 0-300 sec adj 5 sec
retransfer time delay3 0-30 minutes adj 10 minutes
stop/cool down delay4 0-30 minutes adj 10 minutes
neutral delay (600A switch & above) 0-64 sec 10 sec
under voltage sensing of utility5 70-90% D.O. adj
90-95% P.U. adj
85% D.O.
90% P.U.
frequency sensing of utility  ---  ---
voltage sensing of generator (1 leg) 75% D.O.
90% P.U.
 
frequency sensing of generator 75% D.O.
90% P.U.
 
generator test with or without load without
generator exercise with or without load
7-28 days
without
28 days
Exerciser Clock integral to controller
Battery Charger included
Wire Size Ranges #14 to 2/0 AWG (1 per line, 3 neutral)
UL Withstand & Closing Ratings 22,000 amps when protected with:
  Square D QB, QD, QG, QJ breakers up to 125A or
  Eaton JDC, KDC breakers up to 100A
Nominal Dimensions (H x W x D) 24" x 17" x 7"

NOTES:
1The start time delay prevents nuisance generator starts during momentary utility power variations.
2Transfer time delay allows generator set to stabilize before load is applied.
3Retransfer delay prevents needless power interruption if return of utility power is momentary.
4Stop delay allows gradual generator set cool down.
5Undervoltage sensing of utility supply provides reliable starting of generator set during brownout conditions.

 

Customers who purchased this product also ordered:
(click underlined words to see product pages)

 

 

 

 




Item Number: RSS100
Price: $1,263
Price last updated 3/30/2023
Shipping Weight: 47 lbs.
This item normally ships in approximately 6 weeks or less.

 

Are YOU ready for the next power outage?

 1 Videos
 2 Outage Archives
 3 Utility Industry
 4 Why You Need Backup
 5 Personal Stories
 6 NoOutage Configurations
 7 Safety
 8 Sizing for Your Needs
 9 Voltage Drop Calculator
10 Test Reports
11 Placing Order
12 Equipment Leasing
13 Books & Videos  
14 Financing
15 Frequently Asked
16 Future Technologies
17 Electricity Glossary
18 Help with Plug Types
19 Who We Are
20 Why Buy Here
21 Our Customers
22 Pick a Contractor
23 Privacy Promise
24 Safe Shopping Guarantee
25 Terms & Conditions
26 What's New
27 Contacting Us
28 Parts Lookup
29 Parts & Service
30 Made in USA
31 Links

We welcome your feedback or questions.  Click here to contact us.
See our Terms & Conditions before using information or ordering from this web site.
Copyright © 1999-2023 NoOutage.com LLC.  All rights reserved.