NATS22A

PRELIMINARY INFORMATION SUBJECT TO CHANGE


Kutai-ATS245.jpg (23171 bytes)   Kutai-ATS245dims.gif (44943 bytes)   
Click thumbnail image above to enlarge

Universal Controller for
Automatic Transfer Switches
240 Vac 1 or 3 phase

(field installable and programmable)


An Automatic Transfer Switch (ATS) transfers critical electrical loads from the normal utility (grid) source to a standby generator backup source. When the grid is restored it automatically switches the load back. The controller is the "brains" that performs and the monitoring of the two sources, the starting and stopping of the standby generator and the transfer control.

The NATS22A is a multi-function programmable logic automatic transfer switch controller. It is suitable for single and 3 phase systems and includes all necessary monitoring and protections. It works with most transfer switches in existence, including the recently discontinued GE Zenith MX-60 controller. Unlike some other controllers, the NATS22A does not require 12 Vdc control power and therefore an extra wire pair from the engine starting battery is NOT required.

Now you do not have to replace a perfectly good transfer switch simply because the original manufacturer will no longer sell a replacement for a non-working controller.


FEATURES


AS REPLACEMENT FOR GE ZENITH MX-60

When the NATS22A is used as a replacement for the MX-50 or MX-60 controllers on an existing ZTX switch a summary of the installation steps would be as follows. Supplementary instructions are provided with order to aid in identifying the wires and making the changes. If the controller is ordered with installation kit the following items will normally be provided: control wire, butt splices, ties, fuses.

  1. mark the nine control wires at the harness interconnect plug at the existing MX controller board

  2. cut the plug off the harness

  3. trace two of those wires back to the position limit switches on the power contactor and disconnect them

  4. locate two specific Form-C coil clearing limit switches and verify their polarities

  5. reconnect the two wires from step 3 to these two limit switches

  6. select a location for the new controller (usually on front cover), make the cutout and mount the controller

  7. extend the length of the 8-conductor wire harness to the new controller using additional wire and butt splices

  8. terminate the wire harness at the controller and add the necessary wire jumpers

  9. connect the engine start wires

  10. make any programming changes and test the system

  11. mark the old MX touch-pad as non-functional or obscure it with a cover

 
AS REPLACEMENT FOR OTHER CONTROLLERS

When the NATS22A is used as a replacement for other types of controllers a control wiring diagram is needed for the switch. This can sometimes be found in the original manufacturer's instruction manual for the switch or it may be pasted inside the cover. If it is not available then it will have to be created by manually tracing the wiring. The number and operating Voltage of the coils or solenoids must also be known. With this information in-hand it is usually possible incorporate the NATS22A into the switch.


NATS22A SPECIFICATIONS

 

Description

Value

1 AC Voltage Input Range 50-280 Vac  50/60 Hz
2 AC Voltage Display Range 50-280 Vac  50/60 Hz
3 Frequency Measurement Range 40-75 Hz
4 Remote Start Contact Rating 7 A @ 250 Vac max
5 Normal Source ON Contact Rating 7 A @ 250 Vac max
6 Emergency Source ON Contact Rating 7 A @ 250 Vac max
7 Auxiliary Output Contact Rating 7 A @ 250 Vac max
8 Operating Temperature -20 to +70 C
9 Relative Humidity 90% max
10 Dimensions 4.92"W x 7.09"H x 2.01"D overall
11 Panel Cutout 4.45" x 6.61"
12 Weight 1.96 lbs

 

PROGRAMMABLE SETTINGS

Prog
Line

Description

Range Factory Setting GE Zenith ZTX
MX-60 Setting
Dynagen Vigilant
Controller Setting
1 1 phase or 3 phase system 00 (1 ph) or 01 (3 ph) 01 (3 ph) none (fixed by model) none (fixed by model)
2 ATS control type 00 to 06 00 none (ZTX series only) none (Vigilant series only)
3 TDEN Time Delay Emergency to Normal 00-999 sec 10 sec 300 sec 0-256 sec (10 sec)
4 TDNE Time Delay Normal to Emergency 00-250 sec 10 sec 20 sec (some 5 sec) 0-64 sec (10 sec)
5 TDES Time Delay Engine Start 00-30 sec 5 sec 5 sec (some 3 sec) 0-32 sec (10 sec)
6 TDEC Time Delay Engine Cool down 00-250 sec 30 sec 60 sec 0-256 sec (256 sec)
7 Time Delay in the OFF Position 00-99 sec 5 sec feature not available feature not available
8 Normal Source Over Voltage Protection 11-53 (110-530V) 25 (250V) feature not available 111-118%DO
106-113%PU
9 Normal Source Under Voltage Protection 08-47 (80-470V) 18 (180V) 80%DO
90%PU
82-89%DO (82%)
87-94%PU (87%)
10 Normal Source Voltage Time Delay 00-99 sec 10 sec 3 sec  
11 Normal Source Over Frequency Protection 51-75 Hz 65 Hz feature not available 105-112%
12 Normal Source Under Frequency Protection 40-59 Hz 55 Hz feature not available 88-95% (88%)
13 Normal Source Frequency Time Delay 00-99 sec 10 sec feature not available  
14 Generator Source Over Voltage Protection 11-53 (110-530V) 25 (250V) feature not available 111-118%DO
106-113%PU
15 Generator Source Under Voltage Protection 08-47 (80-470V) 18 (180V) 90%PU 82-89%DO (82%)
87-94%PU (87%)
16 Generator Source Voltage Time Delay 00-99 sec 10 sec feature not available feature not available
17 Generator Source Over Frequency Protection 51-75 Hz 65 Hz feature not available feature not available
18 Generator Source Under Frequency Protection 40-59 Hz 55 Hz 95%PU feature not available
19 Generator Source Frequency Time Delay 00-99 sec 10 sec feature not available feature not available
20 Set Day of Week 1-7 (Mon-Sun) current feature not available user sets
21 Set Hour 00-23 current feature not available user sets
22 Set Minutes 00-59 current feature not available user sets
23 Set Generator Exercise - day 1-7 (Mon-Sun) 6 user sets user sets
24 Set Generator Exercise - start hour 00-23 12 user sets user sets
25 Set Generator Exercise - repeat 01 (weekly)
02 (bi-weekly)
 03 (every 3 wks)
04 (every 4 wks)
01 user sets user sets
26 Set Generator Exercise - duration 00-99 min 00 (off) user sets user sets
27 Set Generator Exercise - load or no load 00 (no load), 01 (load) 00 user sets user sets
28 Test with or without load 00 (no load), 01 (load) 01    
29 Display setting 00 (cyclic), 01 (fixed) 00 feature not available feature not available
30 Program Aux Contact Output - 4 choices 00 transfer failure
01 pre-transfer
02 pre-exerciser
03 ATS in emerg pos
01 pre-transfer feature not available feature not available
31 Pre-transfer/Pre-exercise time delay 00-99 sec 10 sec feature not available feature not available
32 Remote Control 00 disable, 01 enable 00 feature not available feature not available
33 Remote Control - address   00 feature not available feature not available
34 Remote Control - data rate   03 feature not available feature not available
35 AC Voltage Correction 00 no, 01 yes 00 feature not available feature not available
36 Restore Remote Connection Passwords 00 no, 01 yes 00 feature not available feature not available
NOTE: "feature not available" means the OEM controller did NOT have this capability and that the NATS22A is an upgrade

 

PRELIMINARY INFORMATION SUBJECT TO CHANGE

 

 






Item Number: NATS22A
Price: $539
Price last updated 6/21/2022
Shipping Weight: 4 lbs.
This item normally ships in approximately 2 weeks or less.

   

Are YOU ready for the next power outage?

 1 Videos
 2 Outage Archives
 3 Utility Industry
 4 Why You Need Backup
 5 Personal Stories
 6 NoOutage Configurations
 7 Safety
 8 Sizing for Your Needs
 9 Voltage Drop Calculator
10 Test Reports
11 Placing Order
12 Equipment Leasing
13 Books & Videos  
14 Financing
15 Frequently Asked
16 Future Technologies
17 Electricity Glossary
18 Help with Plug Types
19 Who We Are
20 Why Buy Here
21 Our Customers
22 Pick a Contractor
23 Privacy Promise
24 Safe Shopping Guarantee
25 Terms & Conditions
26 What's New
27 Contacting Us
28 Parts Lookup
29 Parts & Service
30 Made in USA
31 Links

We welcome your feedback or questions.  Click here to contact us.
See our Terms & Conditions before using information or ordering from this web site.
Copyright 1999-2022 NoOutage.com LLC.  All rights reserved.