Automatic Transfer Switch
60 amp to 400 Amps or more, single phase
with generator exerciser

 

Zenith ZTG series Automatic Transfer Switches
Commercial and Industrial applications

Powered by TruONE™ technology, Zenith ZTG series automatic transfer switches incorporate switch and controller in one seamless, self-contained unit, reducing the number of wires and connections. This design saves room in the enclosure and minimizes the potential for connection failures. In addition, the design incorporates modular components to reduce downtime and service costs, and an optimum interface for advanced control, connectivity, and energy efficiency.

Easy to Install and Commission
Start up in minutes, not hours.
The new Zenith ZTG series weighs up to 30% less than comparable ATS models but has up to 25% more wire-bending space, making it especially easy for contractors to install. Once sources are connected, an innovative auto-configure function via the HMI sets electrical system parameters in seconds. Because of TruONE™ technology, no additional control wiring or troubleshooting is required onsite. And any programming changes can be done from the HMI with a few keystrokes, making commissioning quick and painless. You can even configure Zenith ZTG on site before installation – using a laptop with Ekip Connect 3 Software, even without any external power supply.

Continuous Operation
Minimize unplanned outages.
Zenith ATS solutions are tested to last up to 6,000 cycles. Based on 10 transfers per month, that’s 50 years of reliable operation! If things ever do go wrong, all critical modules are customer-replaceable to simplify service and significantly reduce downtime and service costs. Say goodbye to blinking lights and stopping motors.


Advanced Data and Connectivity
Make data-driven decisions.
The Zenith ZTG now features cloud-based connectivity through the ABB AbilityTM Energy and Asset Manager. ABB Ability simplifies implementation and use of Zenith transfer switches in coordination with other ABB devices, ensuring one common user interface and one common software environment. Market-leading modular communication with seven protocols ensures easy installation and connectivity now and far into the future.


Optimum Interface
Frustration-free programming.
The LCD HMI on Zenith is easily navigated, password protected, and allows access to features ranging from programmable set-points, time delays, digital I/O and exercisers to switch status, events, and diagnostics. In addition, Ekip Connect computer software is an alternative to the HMI that makes programming a cinch whether you’re in the office, or on-site. With this tool, you can import, export, or modify ATS settings via the USB port located on the HMI with no need to apply power to the unit.

Specs

Switch Current Rating 30 Amps thru 400 Amps and higher
Power Poles 2 pole (3rd neutral pole optional)
Voltage Rating - auto sensing 120/240 V, 1 phase 50/60Hz (up to 480V optional)
Transition Type open transition
Drop out Voltage - both sources selectable 70-98%, 102-120%
Pick up Voltage - both sources selectable 71-99%, 101-119%
Drop out frequency - both sources selectable 80-99%, 101-120%
Pick up frequency - both sources selectable 80.5-99.5%, 100.5-119.5%
Override momentary Source 1 Outage, sec selectable 0-60 sec
Transfer from Source 1 to Source 2 0-3600 sec
Override momentary Source 2 Outage selectable 0-60 sec
Transfer from Source 2 to Source 1, min selectable 0-120
Generator stop delay selectable 0-60 min
Center-OFF delay selectable 0-300 sec
many other time delays included see catalog or instructions
Sensing Voltage loss
Undervoltage
Overvoltage
Phase loss
Voltage unbalance
Over/Under frequency
phase sequence (3 phase)
Generator Exerciser exercise with or without load transfer
Battery Charger not included
Certifications UL 1008 listed up to 480V ac at 50/60 Hz
Seismic certified to IEEE-693-2005 at HIGH level with 2.5 amplification factor
Seismic certified to IBC-2015 at Ip=1.5 for z/h less than or equal to 1
Max Withstand & Closing Ratings
(when used with properly rated circuit breakers at 480V max)
30A to 200A: 150kA with ABB, GE, Schneider, Eaton breakers
260A:  200kA with ABB, GE, Schneider, Eaton breakers
400A: 150kA with ABB breakers
Lug Capacities 30A to 60A: (1)#12 AWG to (1)2/0 per pole
100A to 200A: (1)#6 AWG to (1)300MCM per pole
260A: (1)#2 AWG to 600MCM per pole
400A: (1)#4 AWG to 600MCM per pole, or
         (2)1/0 AWG to 250MCM per pole

NOTES:
1) The
Override momentary Source 1 Outage time delay prevents nuisance generator starts during momentary utility power variations; transfer time delay allows generator set to stabilize before load is applied; Transfer from Source 2 to Source 1 delay prevents needless power interruption if return of utility power is momentary; Generator stop delay allows gradual generator set cool down; Drop out Voltage sensing of utility supply provides reliable starting of generator set during brownout conditions.
2) This switch is not service entrance rated.  This generally means that you need a service entrance rated device between this switch and your power company meter.
3) The standard ZTG contactor comes with 2 power poles to switch the two hot leads of a 120/240V system.  It does NOT switch the neutral, which is acceptable in most areas of the USA.  If there are special requirements in your area that require switching the neutral (as dictated by local codes or electrical inspectors) contact us for a quote.
4) Two normally open auxiliary contacts (1 on the utility and 1 on the emergency contactor) are available as an option.  These can be used for remote indication of the switch position or to turn off loads that should not run when on generator power (such as large heat pumps or central air conditioners).  To order use the drop-down menu.
5) WIRING - This switch provides a single isolated contact for controlling the genset.  The contact closes when the genset is to start and run.

 

Customers who purchased this product also ordered:
(click underlined words to see product pages)

Replacement Parts for Zenith switches.

 

Select options using drop-down menus.  Price adders for extra options will be automatically included in price shown by shopping cart.

ZTG single phase 60A  ZTG single phase 200A
request quote 





Item Number: ZGOG1
Price: $2,993
Price last updated 10/6/2023
Shipping Weight: 105 lbs.
This item normally ships in approximately 8 weeks or less.
   
ZTG single phase 100A ZTG single phase 260A
request quote  request quote 
   
ZTG single phase 160A ZTG single phase 400A
request quote  request quote 
   

 

Are YOU ready for the next power outage?

 1 Videos
 2 Outage Archives
 3 Utility Industry
 4 Why You Need Backup
 5 Personal Stories
 6 NoOutage Configurations
 7 Safety
 8 Sizing for Your Needs
 9 Voltage Drop Calculator
10 Test Reports
11 Placing Order
12 Equipment Leasing
13 Books & Videos  
14 Financing
15 Frequently Asked
16 Future Technologies
17 Electricity Glossary
18 Help with Plug Types
19 Who We Are
20 Why Buy Here
21 Our Customers
22 Pick a Contractor
23 Privacy Promise
24 Safe Shopping Guarantee
25 Terms & Conditions
26 What's New
27 Contacting Us
28 Parts Lookup
29 Parts & Service
30 Made in USA
31 Links

We welcome your feedback or questions.  Click here to contact us.
See our Terms & Conditions before using information or ordering from this web site.
Copyright © 1999-2023 NoOutage.com LLC.  All rights reserved.