ATS10012
Automatic Transfer Switch
100 amp, 120/240V, 1-phase
generator exerciser
When you require a complete basic automatic transfer transfer switch, we have the solution. The Ronk series ATS is designed to UL 1008 and has all the necessary delay timers, voltage sensing, frequency sensing, and generator programmable exerciser clock. Assembled in USA .
POWER IN AN INSTANT
The Ronk Automatic Transfer Switch transfers critical loads automatically in the event of a power outage. Constantly monitoring your business’ power, the Ronk ATS looks for power interruptions or failures caused by an accident or bad weather to instantly switch over to generator power. Leaving your critical machines, devices or appliances operating safely and efficiently.
The Ronk ATS comes standard as NEMA 4 enclosure. Rated UL 1008 in Optional Standby and Emergency Rated options.
Our user-friendly digital control module monitors the voltage and frequency of incoming AC supply. The controller comes factory set with common trips and time delays. It’s easy to change parameters, test and has the option to switch to manual mode if needed..
FEATURES
Comes standard in NEMA 4 enclosure (more stringent than NEMA 3R, good for indoor and outdoor use)
Rated UL 1008
Available in Optional Standby in 100A and 200A single-phase
Available in Emergency Power System in 400A and 600A single-phase and in 100A through 600A three-phase
User-friendly digital controller comes factory set with common trips and time delays
Easy to change parameters, test and has the option to switch to manual mode if needed.
CONTROL AT YOUR FINGERTIPS
The controller will monitor the voltage and frequency of the incoming AC supply from two different sources, which could be from generator or mains (utility), or a combination of both. The module will monitor S1 (source 1) and in the event of a failure will issue a start command to S2 (source 2). Once S2 is available and producing an output within limits, the module will control the transfer device and switch the load from S1 to S2. Once the S1 supply returns to within limits, the module will command a load return to S1 and shut down S2.
Specifications
Switch Current Rating | 100 amps, 2 pole | ||
Voltage Rating | 120/240V, 1 phase, 60Hz standard | ||
Temperature Ratings | 113°F (45°C) 100% current, derate at higher temperatures, do not exceed 158°F (70°C) | ||
Control Voltage Rating | 8 to 35 Vdc continuous (168 mA @ 12 Vdc or 80 mA @ 24 Vdc) | ||
Generator Run Start Contact Rating | 8 Amp, 35 Vdc maximum | ||
Control Features (see note 1) Setting adjustments made using buttons and LCD on face of DSE331 Controller. Details contained in Installation & User Manuals. KEY: P.U. = pickup D.O. = dropout |
Function | Adjustable Range | Factory Setting |
start time delay (TDES) | sec | 13 sec | |
transfer time delay (TDNE) | sec | 21 sec | |
retransfer time delay (TDEN) | sec | 270 sec | |
cool down delay (TDEC) | 0- sec | 270 sec | |
neutral delay (600A switch & above) | 0- sec | 10 sec | |
voltage sensing of utility | D.O. above/below P.U. above/below |
10% 5% |
|
frequency sensing of utility | D.O. above/below P.U. above/below |
6 Hz 2 Hz |
|
voltage sensing of generator | D.O. above/below P.U. above/below |
14% 10% |
|
frequency sensing of generator | D.O. above/below P.U. above/below |
6 Hz 6 Hz |
|
Exerciser Clock | field adjustable, factory set for weekly Saturday noon 10 minute load exercise | ||
Battery Charger | not included (Order separately if required. Recommended if exercise intervals are longer than 7 days.) | ||
UL Withstand & Closing Ratings | 10,000 Amps (higher with specific protective devices listed in instructions) | ||
Nominal Dimensions (H x W x D) | 24 x 20 x 6 | ||
Weight | 48 lbs. | ||
Warranty | 2 year factory warranty |
NOTES:
1) The start time delay prevents nuisance generator starts during momentary utility power variations; transfer time delay allows generator set to stabilize before load is applied; retransfer delay prevents needless power interruption if return of utility power is momentary; stop delay allows gradual generator set cool down; undervoltage sensing of utility supply provides reliable starting of generator set during brownout conditions.
2) This switch is not service entrance rated. This generally means that you need a service entrance rated disconnect between this switch and your utility meter.
Customers who purchased this product also ordered:
(click underlined words to see product pages)Battery charger BATTEND022
Item Number: ATS10012
Price: $2,096
Price last updated 12/1/2023
Shipping Weight: 48 lbs.
This item normally ships in approximately 2-4 weeks or less.