Page last updated Oct 20, 2021 @ 10:04pm
PATRIOT
THIS MODEL DISCONTINUED AND REPLACED WITH
SIMILAR 2900 SERIES
![]()
photo
load bank digital meter
click on thumbnail
image above to enlarge
Resistive Load Bank
500-700kW max, 120-480VAC, 1 or 3phase
This PATRIOT Load Bank is a portable, self-contained unit that simulates electrical loads. It is ideal for routine load testing of standby diesel generating systems at remote sites or for factory production line testing of (UPS) Uninterruptible Power Supplies, turbines, or engine generator sets. This model provides resistive loading up to 700 KW at either 240/480 Volts AC in a convenient, and easy-to-use package..
The load bank is available in four versions:
500kW at 240 or 480Vac (selectable) 3-phase with 50kW step resolution
500kW at 240 or 480Vac (selectable) 3-phase with 5kW step resolution
700kW at 240 or 480Vac (selectable) 3-phase with 50kW step resolution
700kW at 240 or 480Vac (selectable) 3-phase with 5kW step resolutionControl Power: These load banks require control/blower power of 120 VAC, 1 phase, 60 Hz (line cord provided). If 120 VAC, 1 phase, 60 Hz is not readily available, a control power transformer is available as an option.
Blower Power: Blower power is derived from the power source under test.
Digital Metering: Avtron Advanced Digital Monitoring System (ADMS) is provided for faceplate display of Volts, Amps, Frequency, or KW. Includes Communicator EXT data-logging software which allows real time data acquisition and trending of all meter parameters from your laptop PC or PDA. An infrared/USB interface cable is included for "Plug and Play" convenience..
Features include:
- Portable for load testing at multipe Sites
- Compact easy to transport and operate
- Extra large load capacity up to 700kW
- Rugged aluminized steel enclosure with castors
- Convenient operator controls with digital metering and data logging software
.
Specs
| Maximum Capacity | 500 kW or 700 kW models |
| Minimum Load Step Resolution | 5 kW or 50 kW models |
| Voltage | 240 or 480 VAC selectable |
| Phases | 3 |
| Blower and Control Power | 120VAC 1-phase 50/60 Hz required. Detachable line cord provided. |
| Controls and Indicators |
- blower power ON/OFF - master load ON/OFF switch - load voltage selector switch - load step switches, toggle type - over temperature protection |
| Overall Dimensions (L x W x H) |
60.5" x 33.5" x 75" |
Note: Other models with international 50 Hz voltages or custom DC voltages also available.
Are YOU ready for the next power outage?